Part Number Hot Search : 
2C128 300S12 KSP44TA 04B27 CY7C656X 87C51 1N5397 15D100KG
Product Description
Full Text Search
 

To Download J80K400-240 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  ? complete input to output ?galvanic? isolation. ? almost silent high frequency operation ? push button starting and stopping ? diagnostic panel with lcd and led display ? soft start on inverter ? overload and short circuit protection ? optional solid state transfer switch built in ? optional maintenance bypass switch built in ? optional dc input circuit breaker ? remote isolated dry relay contacts ? available options to meet military specs including mil-std-461, mil-std-167, mil-std-810 ? all electronics are built in modular front access and front removable sub assemblies for easy service and maintenance nova inverters are high-reliability power sources specifically designed for demanding applications in high shock, vibration, humidity, and emi environments. they can be built to meet mil-std-810, mil-std- 1399, mil-std-1472, mil-std-461, and other standards optionally. military programs, vehicular, shipboard ac power from battery communications shelters utility applications emergency lighting features applications rugged single & three phase inverters 120, 240 and 350 vdc nominal input pure sine-wave output galvanic isolated jupiter series www.novaelectric.com novasales@theallpower.com n o v a v v e le ctric a nova electric a leader in inverter technology since 1966 - 500va-500+kva rugged single & three phase inverters 120, 240 and 350 vdc nominal input pure sine-wave output galvanic isolated jupiter series
the inverter includes an rs232 communication option called upscom. this is an rs232 connection to a pc that can monitor the information related to the inverter output and any abnormal conditions that have occurred in real time. standard commercially available software is provided. the rs232 feature is included at no additional charge. front panel lcd display and led indicators - these will report all inverter parameters, including input and output voltages, currents, frequency, dc voltage and many other functions. lcd display - real time status, data, and historical events are displayed via status leds - a series of leds representing all the important status information of the inverter provide information to the user. these leds are especially important when abnormal conditions occur. since these leds are located behind the transparent window, the user can see them clearly without opening the door. led descriptions are as follows: inverter on ? inverter is running normally. inverter ss ? inverter static switch is on while the reserve static switch is opened (off). short circuit ? inverter output is in short circuit state. fuse / overtemp sd ? inverter has shut down due to either open fuse open or overtemperature. inverter fail shut down ? inverter has shut down due to low inverter ac output. bypass on shut down ? inverter shut down due closed byp ass breaker (while inverter running). high dc shut down ? inverter shut down due to high dc bus. overload shut down ? inverter shut down due to overload of the inverter for a period greater than the inverter can accept. the inverter will start after 7 seconds. 70% load ? load connected to the output is over 70% of the inverter rating. 110% load ? load connected to the output is over 110% of the inverter rating. 125% load ? load connected to the output is over 125% of the inverter rating. 150% load ? load connected to the output is over 150% of the inverter rating. reserve ac fail ? reserve ac magnitude is out of range. reserve freq fail ? reserve frequency is out of range. battery low - dc bus (or battery) is lower than specified range. low battery shut down will occur soon. battery low shut down ? inverter shut down due to dc bus (or battery) lower than the acceptable dc voltage of the inverter. ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? high dc ? dc voltage over the acceptable dc voltage of the inverter. emergency stop ? inverter shutdown activated by emergency stop switch. data line ? blinks when data is transmitted to or received from the communication port. audible alarm ? the audible alarm will beep under one of the following inverter is overloaded : 110% beep once every 3 seconds 125% beep once every second 150% beep twice every second inverter is short circuited ? beeps continuously fuse open ? beeps continuously heat sink over temperature ? beeps continuously high dc shutdown ? beeps continuously bypass on stop ? beeps continuously emergency on stop ? beeps continuously. the buzzer will also beep once every time the inverter is switched on or off to acknowledge to the user that his key entry is valid and accepted. ? ? ? ? ? ? ? ? ? ? monitoring features the lcd display. the inverter parameters, real time clock, and buzzer alarm also can be set through this lcd. the lcd is backlit by leds for easy visuals. jupiter series dc-ac inverters communications options some popular communications options available at additional cost include the following: upscan: this is a hand held remote display and control module with lcd and led display that can monitor up to 99 inverter units via rs-485 at a remote distance of up to 3,000 feet. netagent: this provides capability to monitor the inverter over the internet. it includes the appropriate additional snmp card and microprocessor. the software required is provided separately. upscall: this is a modem that will automatically dial out to a specified other options dc input breaker option ? the optional dc input breaker disconnect is offered to provide protection for the input. shock mount option ? the cabinet can be shock mounted using optional rubber or coil type isolators. this will enable the unit to withstand shock levels as speci ed in mil-s-901 ruggedizing option ? this option will add conformal coating and other additional internal structural members to allow the unit to meet many portions of mil-std-810 including shock, vibration, and humidity. turn on service option ? we offer a turn on service that will ensure the inverter has been properly installed and the full warranty is in effect (failures caused by incorrect installation are not covered by the warranty.) if this option is selected, the customer will also automatically receive an additional 3 months added to the warranty at no additional charge. spare parts kit option ? we offer a spare parts package that includes one of each board, spare fuses, spare semiconductors, and spare fans. these spare part kits are priced lower when ordered with the initial order than if they are ordered later on. drip shield options ? this option offers protection against falling or dripping liquids. customized epo ? this feature can be customized to trip off current breakers or perform other inhibits depending customer needs. number when an abnormal situation occurs. conditions: warning leds ? when abnormal condition occurs, these leds will light to warn the user of the cause of the fault condition. therefore all these leds are off under normal condition. these leds are: rect ac fail ? rectifier ac input is abnormal either due to ac magnitude out of the range or phase rotation error; rectifier shut down. reserve fail ? reserve ac input is abnormal either due to ac magnitude out of range or frequency out of range. fuse/temp - either inverter fuse is open or over temperature has occurred. overload ? output is overloaded by over 110%, 125% or 150% high dc ? this led will light as long as the dc voltage is over 430vdc. bat low ? this led will light when the dc voltage is lower than 320vdc. bat low stop ? this led will light when the dc voltage is lower than 295vdc, inverter on is inhibited. fault ? the inverter is off due to abnormal conditions such as overload, short circuit, high dc, fuse over temperature, bypass breaker on emergency stop.
specifications for jupiter 120 vdc single & 3-phase inverter series standard product listing - 120 vdc *for input circuit breaker, add ?b1? suffix to part number for solid state transfer switch, add ?y11? suffix to part number jupiter series dc-ac inverters <110% 110-125% 125-150% >150% output power factor yes mov / input & output ( fcc class a) output true galvanic isola on monitoring 1~99 units simultaneously / dry contact, rs-232, rs-485 (op onal) yes dc input / single or 3-phase output 3-phase models please specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120 delta | 220 delta | 240 delta | 380 delta | 480 delta or single phase please specify | 120 vac | 220 vac | 240 vac | 480 vac pure sinewave 0.7 lead to 0.7 lag +/- 5% (alternate ranges o ? ered on special order) 0%-95% (non-condensing) up to 1500 m above sea level yes phase inverter thd (linear load) output voltage (vac) op onal same as ac output. (di ? erent voltages are available upon request) voltage range overload e ? ciency (100% load) wave form phase shi under 100% unbalanced load output frequency (free running) frequency lock range static switch lightning / emc filter galvanic isola on remote control / communica on interface humidity al tude en50091-1,-2 short circuit protec on led, lcd, audible alarm mains <-> inverter audible noise temperature input frequency range +/- 5% (wider ranges o ? ered, please consult factory) 0 ms (true online) -10c to +50c (extended ranges available) <65 dba (at 1m) please specify: 50 hz or 60 hz or 400 hz (crystal controlled) <0.5% (3-phase models) 2% typical 3% max con nuous 15 minutes 10 minutes 1 minute 89 - 90% output continous size vac output power (h"x w"x l") j10k60- 120 120 60 hz 10 kva/ 8 kw 770lbs. 63 x 22 x 31.5 j15k60- 120 120 60 hz 15 kva/ 12kw 880lbs. 63 x 22 x 31.5 j20k60- 120 120 60 hz 20 kva/ 16 kw 880lbs. 63 x 22 x 31.5 j30k60- 120 120 60 hz 30 kva/ 24 kw 1650lbs. 63 x 43.5 x 31.5 j40k60- 120 120 60 hz 40 kva/ 32 kw 1760lbs. 63 x 43.5 x 31.5 j50k60- 120 120 60 hz 50 kva/ 40 kw 1870lbs. 63 x 43.5 x 31.5 j60k60- 120 120 60 hz 60 kva/ 48 kw 2420lbs. 63 x 87 x 31.5 j80k60- 120 120 60 hz 80 kva/ 64 kw 3080lbs. 63 x 87 x 31.5 j100k60- 120 120 60 hz 100 kva/ 80 kw 3520lbs. 63 x 87 x 31.5 continous size out put power ( h"x w"x l ") j10k60-120(220) 220 50 hz 10 kva/ 8 kw 770lbs. 63 x 22 x 31.5 j15k60-120(220) 220 50 hz 15 kva/ 12kw 880lbs. 63 x 22 x 31.5 j20k60-120(220) 220 50 hz 20 kva/ 16 kw 880lbs. 63 x 22 x 31.5 j30k60-120(220) 220 50 hz 30 kva/ 24 kw 1650lbs. 63 x 43.5 x 31.5 j40k60-120(220) 220 50 hz 40 kva/ 32 kw 1760lbs. 63 x 43.5 x 31.5 j50k60-120(220) 220 50 hz 50 kva/ 40 kw 1870lbs. 63 x 43.5 x 31.5 j60k60-120(220) 220 50 hz 60 kva/ 48 kw 2420lbs. 63 x 87 x 31.5 j80k60-120(220) 220 50 hz 80 kva/ 64 kw 3080lbs. 63 x 87 x 31.5 j100k60-120(220) 220 50 hz 100 kva/ 80 kw 3520lbs. 63 x 87 x 31.5 continous size out put power ( h"x w"x l ") j10k400-120 115 400hz 10 kva/ 8 kw 770lbs. 63 x 22 x 31.5 j15k400-120 115 400hz 15 kva/ 12kw 880lbs. 63 x 22 x 31.5 j20k400-120 115 400hz 20 kva/ 16 kw 880lbs. 63 x 22 x 31.5 j30k400-120 115 400hz 30 kva/ 24 kw 1650lbs. 63 x 43.5 x 31.5 j40k400-120 115 400hz 40 kva/ 32 kw 1760lbs. 63 x 43.5 x 31.5 j50k400-120 115 400hz 50 kva/ 40 kw 1870lbs. 63 x 43.5 x 31.5 j60k400-120 115 400hz 60 kva/ 48 kw 2420lbs. 63 x 87 x 31.5 j80k400-120 115 400hz 80 kva/ 64 kw 3080lbs. 63 x 87 x 31.5 j100k400-120 115 400hz 100 kva/ 80 kw 3520lbs. 63 x 87 x 31.5 j10k3/6-120 (120/208) 120/208 60 10kva / 8kw 770 63x22x31.5 j10k3/5-120 (220/380) 220/380 50 10kva / 8kw 770 63x22x31.5 j10k3/4-120 (115/200) 115/200 400 10kva / 8kw 770 63x22x31.5 j20k3/6-120 (120/208) 120/208 60 20kva / 16kw 880 63x22x31.5 j20k3/5-120 (220/380) 220/380 50 20kva / 16kw 880 63x22x31.5 j20k3/4-120 (115/200) 115/200 400 20kva / 16kw 880 63x22x31.5 j30k3/6-120 (120/208) 120/208 60 30kva / 24kw 1650 63x43.5x31.5 j30k3/5-120 (220/380) 220/380 50 30kva / 24kw 1650 63x43.5x31.5 j30k3/4-120 (115/200) 115/200 400 30kva / 24kw 1650 63x43.5x31.5 j40k3/6-120(120/208) 120/208 60 40kva / 32kw 1760 63x43.5x31.5 j40k3/5-120(220/380) 220/380 50 40kva/ 32kw 1760 63x43.5x31.5 j40k3/4-120 (115/200) 115/200 400 40kva/ 32kw 1760 63x43.5x31.5 j50k3/6-120 (120/208) 120/208 60 50kva / 40kw 1870 63x43.5x31.5 j50k3/5-120 (220/380) 220/380 50 50kva / 40kw 1870 63x43.5x31.5 j50k3/4-120 (115/200) 115/200 400 50kva / 40kw 1870 63x43.5x31.5 j60k3/6-120 (120/208) 120/208 60 60kva / 48kw 2420 63x87x31.5 j60k3/5-120 (220/380) 220/380 50 60kva / 48kw 2420 63x87x31.5 j60k3/4-120 (115/200) 115/200 400 60kva / 48kw 2420 63x87x31.5 j80k3/6-120 (120/208) 120/208 60 80kva / 64kw 3080 63x87x31.5 j80k3/5-120 (220/380) 220/380 50 80kva / 64kw 3080 63x87x31.5 j80k3/4-120 (115/200) 115/200 400 80kva / 64kw 3080 63x22x31.5 j100k3/6-120 (120/208) 120/208 60 100kva / 80kw 3520 63x87x31.5 j100k3/5-120 (220/380) 220/380 50 100kva / 80kw 3520 63x87x31.5 j100k3/4-120 (115/200) 115/200 400 100kva / 80kw 3520 63x87x31.5 models output freq. weight 60hz singl e phase m odel s outputv ac output freq. weight size (h x w x l) ( inches) 400 hz models outputv ac output freq. weight 3-phase models output vac output freq (hz) continuous output power a pprox. weight (lb)
jupiter series dc-ac inverters specifications for jupiter 240 vdc standard product listing - 240 vdc <110% 110-125% 125-150% >150% <65 dba (at 1m) <67 dba (at 1m) al tude en50091-1,-2 short circuit protec on voltage range mains <-> inverter audible noise temperature phase inverter thd (linear load) output voltage (vac) op onal same as ac output. (di ? erent voltages are available upon request) input frequency range +/- 5% (wider ranges o ? ered, please consult factory) wave form phase shi under 100% unbalanced load output frequency (free running) frequency lock range output power factor static switch dc input / single or 3-phase output 3-phase models please specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120 delta | 220 delta | 240 delta | 380 delta | 480 delta or single phase please specify | 120 vac | 220 vac | 240 vac | 480 vac sinewave 0.7 lead to 0.7 lag +/- 5% (alternate ranges o ? ered on special order) please specify: 50 hz or 60 hz or 400 hz (crystal controlled) <0.5% 2% typical 3% max overload e ? ciency (100% load) yes mov / input & output ( fcc class a) input and output true galvanic isola on con nuous 15 minutes 10 minutes 1 minute 90 - 91% typical 0 ms (true online) -10c to +50c (extended ranges available) 0%-95% (non-condensing) up to 1500 m above sea level yes humidity monitoring 1~99 units simultaneously / dry contact, rs-232, rs-485 (op onal) led, lcd, audible alarm yes lightning / emc filter galvanic isola on remote control / communica on interface single & 3-phase inverter series out put cont inous siz e vac output power (h"x w"x l") j10k60-240 120 60 hz 10 kva/ 8 kw 638lbs. 63 x 22 x 31.5 j20k60-240 120 60 hz 20 kva/ 16 kw 770lbs. 63 x 22 x 31.5 j30k60-240 120 60 hz 30 kva/ 24 kw 990lbs. 63 x 22 x 31.5 j40k60-240 120 60 hz 40 kva/ 32 kw 1210lbs. 63 x 22 x 31.5 j50k60-240 120 60 hz 50 kva/ 40 kw 1650lbs. 63 x 43.5 x 31.5 j60k60-240 120 60 hz 60 kva/ 48 kw 1870lbs. 63 x 43.5 x 31.5 j80k60-240 120 60 hz 80 kva/ 64 kw 2090lbs. 63 x 87 x 31.5 j100k60-240 120 60 hz 100 kva/ 80 kw 2420lbs. 63 x 87 x 31.5 j120k60 240 120 60 hz 120 kva/ 96 kw 3300lbs. 63 x 87 x 31.5 j160k60-240 120 60 hz 160 kva/ 128 kw 3960lbs. 63 x 87 x 31.5 j200k60-240 120 60 hz 200 kva/ 160 kw 4840lbs. 63 x 87 x 31.5 out put cont inous siz e vac output power (h"x w"x l") j10k50- 240(220) 220 50hz 10 kva/ 8 kw 638lbs. 63 x 22 x 31.5 j20k50- 240(220) 220 50hz 20 kva/ 16 kw 770lbs. 63 x 22 x 31.5 j30k50- 240(220) 220 50hz 30 kva/ 24 kw 990lbs. 63 x 22 x 31.5 j40k50- 240(220) 220 50hz 40 kva/ 32 kw 1210lbs. 63 x 22 x 31.5 j50k50- 240(220) 220 50hz 50 kva/ 40 kw 1650lbs. 63 x 43.5 x 31.5 j60k50- 240 (220) 220 50hz 60 kva/ 48 kw 1870lbs. 63 x 43.5 x 31.5 j80k50- 240(220) 220 50hz 80 kva/ 64 kw 2090lbs. 63 x 43.5 x 31.5 j100k50- 240(220) 220 50hz 100 kva/ 80 kw 2420lbs. 63 x 43.5 x 31.5 j120k50- 240(220) 220 50hz 120 kva/ 96 kw 3300lbs. 63 x 87 x 31.5 j160k50- 240(220) 220 50hz 160kva/ 128 kw 3960lbs. 63 x 87 x 31.5 j200k50- 240(220) 220 50hz 200 kva/ 160 kw 4840lbs. 63 x 87 x 31.5 out put cont inous siz e vac output power (h"x w"x l") j10k400- 240 115 400hz 10 kva/ 8 kw 638lbs. 63 x 22 x 31.5 j20k400- 240 115 400hz 20 kva/ 16 kw 770lbs. 63 x 22 x 31.5 j30k400- 240 115 400hz 30 kva/ 24 kw 990lbs. 63 x 22 x 31.5 j40k400- 240 115 400hz 40 kva/ 32 kw 1210lbs. 63 x 22 x 31.5 j50k400- 240 115 400hz 50 kva/ 40 kw 1650lbs. 63 x 43.5 x 31.5 j60k400- 240 115 400hz 60 kva/ 48 kw 1870lbs. 63 x 43.5 x 31.5 j80k400- 240 115 400hz 80 kva/ 64 kw 2090lbs. 63 x 43.5 x 31.5 j100k400- 240 115 400hz 100 kva/ 80 kw 2420lbs. 63 x 43.5 x 31.5 j120k400- 240 115 400hz 120 kva/ 96 kw 3300lbs. 63 x 87 x 31.5 j160k400- 240 115 400hz 160kva/ 128 kw 3960lbs. 63 x 87 x 31.5 j200k400- 240 115 400hz 200 kva/ 160 kw 4840lbs. 63 x 87 x 31.5 3- pha se output output continuous a pprox. siz e models* v a c freq output weight ( h x w x d) ( hz ) power ( lb) ( inches) j10k3/6-240(120/208) 120/208 60 10kva 638 63x22x31.5 j10k3/5-240(220/380) 220/380 50 10kva 638 63x22x31.5 j20k3/6-240(120/208) 120/208 60 20kva 770 63x22x31.5 j20k3/5-240(220/380) 220/380 60 20kva 770 63x22x31.5 j30k3/6-240(120/208) 120/208 60 30kva 990 63x22x31.5 j30k3/5-240 (220/380) 220/380 50 30kva 990 63x22x31.5 j40k3/6-240(120/208) 120/208 60 40kva 1210 63x22x31.5 j40k3/5-240(220/380) 220/380 50 40kva 1210 63x22x31.5 j50k3/6-240(120/208) 120/208 60 50kva 1650 63x44x31.5 j50k3/5-240(220/380) 220/380 50 50kva 1650 63x44x31.5 j60k3/6-240(120/208) 120/208 60 60kva 1870 63x43.5x31.5 j60k3/5-240(220/380) 220/380 50 60kva 1870 63x43.5x31.5 j80k3/6-240(120/208) 120/208 60 80kva 2090 63x43.5x31.5 j80k3/5-240(220/380) 220/380 50 80kva 2090 63x43.5x31.5 j100k3/6-240(120/208) 120/208 60 100kva 2420 63x43.5x31.5 j100k3/5-240(220/380) 220/380 50 100kva 2420 63x43.5x31.5 j120k3/6-240(120/208) 120/208 60 120kva 3300 63x87x31.5 j120k3/5-240(220/380) 220/380 50 120kva 3300 63x87x31.5 j160k3/6-240(120/208) 120/208 60 160kva 3960 63x87x31.5 j160k3/5-240(220/380) 220/380 50 160kva 3960 63x87x31.5 j200k3/6-240(120/208) 120/208 60 200kva 4840 63x87x31.5 j200k3/5-240(220/380) 220/380 50 200kva 4840 63x87x31.5 400hz models output freq. weight 60hz m odel s output freq. weight 50 hz m odel s output freq. weight
jupiter series dc-ac inverters specifications for jupiter 350 vdc standard product listing - 350 vdc *for input circuit breaker, add ?b1? suffix to part number for solid state transfer switch, add ?y11? suffix to part number single & 3-phase inverter series <110% 110-125% 125-150% >150% <65 dba (at 1m) <67 dba (at 1m) led, lcd, audible alarm yes short circuit protec on voltage range mains <-> inverter audible noise temperature yes mov / input & output ( fcc class a) input and output true galvanic isola on phase inverter thd (linear load) output voltage (vac) op onal same as ac output. (di ? erent voltages are available upon request) wave form phase shi under 100% unbalanced load output frequency (free running) frequency lock range output power factor 10 minutes 1 minute 90 - 91% typical overload e ? ciency (100% load) please specify: 50 hz or 60 hz or 400 hz (crystal controlled) con nuous 15 minutes dc input / single or 3-phase output 3-phase models please specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120 delta | 220 delta | 240 delta | 380 delta | 480 delta or single phase please specify | 120 vac | 220 vac | 240 vac | 480 vac sinewave 0.7 lead to 0.7 lag +/- 5% (alternate ranges o ? ered on special order) +/- 5% (wider ranges o ? ered, please consult factory) input frequency range monitoring 1~99 units simultaneously / dry contact, rs-232, rs-485 (op onal) static switch 0 ms (true online) 0-50oc (32-122of) (other ranges available) 0%-95% (non-condensing) up to 1500 m above sea level yes lightning / emc filter galvanic isola on remote control / communica on interface humidity al tude en50091-1,-2 <0.5% 2% typical 3% max 3- pha se output output continuous a pprox. siz e models* v a c freq output weight ( h x w x d) ( hz ) power ( lb) ( inches) j10k3/5-350(220/380) 220/380 50 10kva 660 63x22x31.5 j10k3/6-350(120/208) 120/208 60 10kva 640 63x22x31.5 j10k3/4-350(115/200) 115/200 400 10kva 640 63x22x31.5 j20k3/5-350(220/380) 220/380 50 20kva 790 63x22x31.5 j20k3/6-350(120/208) 120/208 60 20kva 770 63x22x31.5 j20k3/4-350(115/200) 115/200 400 20kva 770 63x22x31.5 j30k3/5-350(220/380) 220/380 50 30kva 1010 63x22x31.5 j30k3/6-350(120/208) 120/208 60 30kva 990 63x22x31.5 j30k3/4-350(115/200) 115/200 400 30kva 990 63x22x31.5 j40k3/5-350(220/380) 220/380 50 40kva 1230 63x22x31.5 j40k3/6-350(120/208) 120/208 60 40kva 1210 63x22x31.5 j40k3/4-350(115/200) 115/200 400 40kva 1210 63x22x31.5 j50k3/5-350(220/380) 220/380 50 50kva 1580 63x22x31.5 j50k3/6-350(120/208) 120/208 60 50kva 1540 63x22x31.5 j50k3/4-350(115/200) 115/200 400 50kva 1540 63x22x31.5 j60k3/5-350(220/380) 220/380 50 60kva 1800 63x22x31.5 j60k3/6-350(120/208) 120/208 60 60kva 1760 63x22x31.5 j60k3/4-350(115/200) 115/200 400 60kva 1760 63x22x31.5 j80k3/5-350(220/380) 220/380 50 80kva 2040 63x43.5x31.5 j80k3/6-350(120/208) 120/208 60 80kva 1980 63x43.5x31.5 j80k3/4-350(115/200) 115/200 400 80kva 1980 63x43.5x31.5 j100k3/5-350(220/380) 220/380 50 100kva 2490 63x43.5x31.5 j100k3/6-350(120/208) 120/208 60 100kva 2420 63x43.5x31.5 j100k3/4-350(115/200) 115/200 400 100kva 2420 63x43.5x31.5 j120k3/5-350(220/380) 220/380 50 120kva 3410 63x43.5x31.5 j120k3/6-350(120/208) 120/208 60 120kva 3300 63x43.5x31.5 j120k3/4-350(115/200) 115/200 400 120kva 3300 63x43.5x31.5 j160k3/5-350(220/380) 220/380 50 160kva 4100 63x43.5x31.5 j160k3/6-350(120/208) 120/208 60 160kva 3960 63x43.5x31.5 j160k3/4-350(115/200) 115/200 400 160kva 3960 63x43.5x31.5 j200k3/5-350(220/380) 220/380 50 200kva 4900 63x87x31.5 j200k3/6-350(120/208) 120/208 60 200kva 4840 63x87x31.5 j200k3/4-350(115/200) 115/200 400 200kva 4840 63x87x31.5 j240k3/5-350(220/380) 220/380 50 240kva 5760 63x87x31.5 j240k3/6-350(120/208) 120/208 60 240kva 5760 63x87x31.5 j240k3/4-350(115/200) 115/200 400 240kva 5760 63x87x31.5 j300k3/5-350(220/380) 220/380 50 300kva 6160 63x87x31.5 j300k3/6-350(120/208) 120/208 60 300kva 6160 63x87x31.5 j300k3/4-350(115/200) 115/200 400 300kva 6160 63x87x31.5 j320k3/5-350(220/380) 220/380 50 320kva 6510 63x87x31.5 j320k3/6-350(120/208) 120/208 60 320kva 6510 63x87x31.5 j320k3/4-350(115/200) 115/200 400 320kva 6510 63x87x31.5
jupiter series dc-ac inverters typical dimension drawings (22? wide)
jupiter series dc-ac inverters typical dimension drawings (43.5? wide)
jupiter series dc-ac inverters typical dimension drawings (87? wide)
jupiter series dc-ac inverters reliability and serviceability (mtbf & mttr) reliability is a feature that is designed and integrated into every piece of equipment that carries the nova electric name. th is is accomplished by utilizing state of the art circuitry which substantially reduces the total number of components (especially heat producing components). the result is greater ef ciency, high reliability and low cost. a study of installed units has indicated an mtbf of over 100,000 hours! mtbf gures are based upon ground xed normal 25-degree ambient temperature and proper and preventive maintenance. the mttr for all items offered is approximately 30 minutes. part of the maintenance and repair philosophy of the units is to us e the bit equipment to aid in fault isolation. at that point, a decision is made to either replace an lru or a component within the power supply with a spare. the construction methods used throughout the jupiter series provide for user friendly service. all circuit boards are plug in and are easily ac cessed from the front of the system. power modules are designed on slide out trays for easy access to all power semiconductors and similar power compon ents. the mttr value speci ed is based upon proper training of local maintenance technicians and engineers. quality control military and rugged commercial (cots) designs all of nova electric?s products feature robust construction quality and rugged designs. they are suitable for demanding milita ry, industrial, and commercial applications. most products can be equipped to meet mil-std-461, mil-std-810, mil-s-901, mil-std-167, mil-std-1399, mil-std-14 72, and other important speci cations as required. please consult the factory about your speci c application. government quality assurance our quality assurance department will be glad to work with the designated government quality assurance representative (gqar) on government or military projects. warranty all nova electric products are warranted against defects in material and workmanship for a period of one year from shipping date. our obligation includes replacing, repairing, or adjusting products (excluding fuses) that prove to be defective during the warranty period. this warranty is fully transferable. if a product is sold to a manufacturer for use in a product for resale, the complete warranty is in force, providing the power system is sold as original equipment. nova electric assumes no liabilities for consequential damages of any kind through the use of misuse of its products by the purchaser or others. no other obligations a re expressed or implied. batteries used with or contained within uninterruptible power supply systems are sold with a ?pass-along ? battery warranty from the battery manufacturer. on site warranty repair is available at extra cost to cover the cost of travel to the work location. extended warranties are also available - please consult the factory for details. nova electric operates under a program of continuous quality improvement (cqi,) as evidenced by its iso-9001 qualify management systems standard certification and decades of compliance to formal quality control systems and procedures that remain in compliance with mil-i-4 5208a inspection and mil-std-45662a calibration requirements. iso registration was granted in 1997 by underwriters laboratories (ul) after first ass essment. operators are certified to j-std-001a and ipc-a-610b class 2 (formerly mil-std-2000) for soldered assemblies. instructors certified by the do d to mil-std-2000 category c are on staff. our cots products benefit from the same rigorous qc procedures as original developed for our military customers. copies of our current iso certificate and factory quality control manual are available upon request.


▲Up To Search▲   

 
Price & Availability of J80K400-240

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X